Product details

FILS circuit breakers RCBOs provide personal and property protection as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. They ensure the protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth residual direct current component of up to mA to earth. Additionally, they offer fault protection against indirect contact, extra protection with I?n 30 mA, and fire protection with I?n 300 mA. They comply with product standards IEC EN 61009-1 VDE 0664-20 and IEC EN 61009-2-1 VDE 0664-21. Areas of application include household, commercial, and industrial uses. The extensive range of accessories provides everything you need for your installation tasks. Numerous approvals make the DS202CR suitable for worldwide use. It is designed for 50 Hz networks with phases 230 AC without a neutral conductor or mobile distribution via Schuko plug 1PN, such as for caravan applications. The rated switching capacity according to IEC EN 61009 is Icn 6 kA. The RCBO DS202CR type is 2-pole protected LS and 2-pole switching. DS202CR B16 A30.